Sirius

Standard Features

Voltage Stabilisation Independent phase control
Output voltage selectable via display , PC and/ or Ethernet * from 210 to 255V (L-N) from 360 to 440V (L-L)
Output voltage accuracy ± 0,5%
Frequency 50Hz ±5% or 60 Hz ±5%
Admitted load variation Up to 100%
Admitted load imbalance 100%
Cooling Natural air ventilatioin. From 35° C aided with fans
Ambient temperature  -25/+45 C
Storage temperature  -25/+60 C
Max relative humidity 95% (non condensing)
Admitted overload 200% 2 min.
Harmonic distortion None introduced
Colour RAL 7035
Protection degree IP 21
User interface 10″ touch panel (multilingual) remotely available via VNC
Installation Indoor
Regulator overload protection Digital control
Communication system Ethernet / USB / MODBUS TCP/ Ip
Overvoltage protection Class I input surge arrestor Class II output surge arrestor Optimal voltage return through supercapacitors in case of blackout